Home / Advisories / KLCERT advisories / KLCERT-20-003: Remote Code Execution on Emerson OpenEnterprise SCADA Server version 2.83 and all versions of OpenEnterprise 3.1 through 3.3.3

KLCERT-20-003: Remote Code Execution on Emerson OpenEnterprise SCADA Server version 2.83 and all versions of OpenEnterprise 3.1 through 3.3.3

Kaspersky publishes information on newly identified vulnerabilities in order to raise user awareness of the IT security threats detected. Kaspersky does not make any guarantees in respect of information received from vendors of products in which vulnerabilities have been identified, which is included in the following sections of the advisory: Affected Products, Vendor Mitigation.

KL-IDS KLCERT-20-003
CVE-IDS CVE-2020-6970
Publication date 2020.02.18
Researcher Roman Lozko, Kaspersky ICS CERT
Description A Heap-based Buffer Overflow was found in Emerson OpenEnterprise SCADA Server version 2.83 (if Modbus or ROC Interfaces have been installed and are in use) and all versions of OpenEnterprise 3.1 through 3.3.3, where a specially crafted script could execute code on the OpenEnterprise Server.
Impact Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code.
Severity
CVSS v3 Base Score: 9.8
Vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Exploitability Remotely
Difficulty Low
User interaction None
Existence of exploit Unknown
Affected products
Affected products OpenEnterprise SCADA Server version 2.83
OpenEnterprise versions 3.1 through 3.3.3
Mitigation
Vendor mitigation Emerson recommends all users upgrade to OpenEnterprise 3.3, Service Pack 4 (3.3.4), to resolve this issue. OpenEnterprise Service Packs are available to users with access to the Emerson SupportNet system (login required). Details will be found in the downloads area.
Timeline Dec 2019 – Vulnerabilities reported
Feb 2020 – Vendor releases patch